digital panel meter market
General
1. Bidirectional Active Energy Measurement:
· Measures both forward and reverse active energy.
· Reverse energy is accumulated with forward energy but is stored separately.
· Switching between communication, time periods, and active energy directions does not affect pulse accumulation accuracy.
2. Four Rate Tariff Settings:
· Supports four tariff rates (peak, high, normal, and low) with eight time periods.
· Time periods can span midnight.
· Time period states are not affected by power outages or harsh working environments.
3. Energy Storage:
· Stores and measures energy by peak, high, normal, low, total, and reverse totals for each rate.
4. Historical Data Storage:
· Stores the frozen data of the previous 12 months, including peak, high, normal, and low energy.
· Default freeze date is the 1st of every month at 00:00, adjustable to any date from the 1st to the 28th.
5. Backup Battery:
· Uses a needle-welded, green, environmentally friendly lithium battery.
· Backup battery can keep the internal clock running normally for at least 10 years during power outages.
6. Communication Interfaces:
· Programming and meter reading can be done through infrared and RS-485 communication interfaces.
7. Energy Indicators:
· Equipped with active energy indicator light and energy pulse output.
8. LCD Display:
· Displays parameters such as time, date, and energy.
· Scrolling display allows setting of display time and content.
· Energy display has six integer digits and one decimal digit.
· Default setting shows all parameters with each parameter displayed for 5 seconds.
9. Hardware Clock Circuit:
· Built-in clock with calendar, timekeeping, and automatic leap year switching functions.
10. Data Retention:
· All stored data is retained for over 10 years during power outages.
· Energy and pulse count remain unchanged during repeated power outages and restorations.
Specification
l Reference Voltage: 220V
l Reference Current:
· 2.5(10)A
· 5(20)A
· 10(40)A
· 20(80)A
l Reference Frequency: 50Hz
l Accuracy Class: Class 1.0
l Pulse Constant: As marked on the nameplate
l Daily Timing Error: ≤0.5s/d (at 25℃ ±2℃)
l Service Life: ≥10 years
l Battery Capacity: 1200mAh
l Infrared Communication Distance: 5m (with a radiation angle less than 15 degrees)
l RS485 Bus Terminals: 256 terminals, Communication Baud Rate: 2400bps
l Starting Current: Under rated voltage, frequency, and power conditions, the starting current is 0.004Ib
l Creep: When the meter circuit has no current and the voltage applied to the circuit is 115% of the rated value, the output pulse should be no more than one.
Dimension