General
DTSY/DSSY Series Three-Phase Electronic Prepaid Energy Meter (referred to as the meter), compliant with GB/T17215 and GB/T18460 standards, utilizes advanced single-chip processing systems for data collection, processing, and storage. Designed for measuring three-phase active energy with a rated frequency of 50Hz.
Key Features:
l Computer-managed, enabling prepaid electricity consumption.
l Can limit maximum power usage within the rated current range (determined by the supply section).
l One meter paired with one card, each card dedicated to its meter; even if the card is lost, electricity consumption data remains intact, and replacement cards can be used.
l Bidirectional data transmission capability between the meter and the card, automatically warning users to recharge before power cutoff.
l Automatically disconnects power when energy consumption reaches zero.
l Incorporates anti-tampering software design to prevent electricity theft.
Specification
Item
|
Item
|
Accuracy
|
Voltage
|
Rated Current
|
Parameter
|
Parameter
|
DTSY DSSY
|
Class 1.0 Class 2.0
|
3X220/380
3X57.7/100
|
1.5(6)
|
Mutual induction
|
1600 3200
|
10(40)
|
Direct
|
400
|
15(60) 20(80)
|
Direct
|
400
|
Basic error (balanced load error limit)
|
Current Value
|
Power Factor (COSΦ)
|
Basic error
|
Direct-connected Meter
|
Through Transformer Meter
|
1
|
2
|
0.5lb≤l<0.1lb
|
0.2lb≤l<0.1lb
|
1
|
±1.5
|
±2.5
|
0.1lb≤l<lmax
|
0.05ln≤l<lmax
|
1
|
±1.0
|
±2.0
|
0.1lb≤l<0.2lb
|
0.05ln≤l<0.1ln
|
0.5(感性)0.8(容性)
|
±1.5
|
±2.5
|
0.2lb≤l<lmax
|
0.1ln≤l<max
|
0.5(感性)0.8(容性)
|
± 1.0
|
± 2.0
|
Others
|
Start-up Conditions
|
Under the conditions of reference voltage, reference frequency, and COS φ = 1.0, with a load current of 0.004Ib (Class 1), 0.005Ib (Class 2), the meter should be able to continuously measure electricity.
|
Creep Conditions
|
With the voltage loop at rated voltage of 115%, and no current in the current loop, the test output of the meter should not produce more than one pulse.
|
Voltage Range
|
Normal operating voltage is 0.9Un-1.1Un, with a limit of 0.8Un-1.15Un.
|
Power Consumption
|
Voltage circuit power consumption ≤ 2W and 10VA, current circuit power consumption ≤ 4.0VA.
|